RCM 700 Sureclose The Failsafe Electro/Hydraulic Actuator consists of a single
acting spring return actuator for fail safe operation, mounted
electric motor, hydraulic pump and reservoir. The actuator is
modified for hydraulic service which includes a bleeder to
purge air from the system. The pump is driven by a totally
enclosed fan cooled single phase motor. In the event of a power loss, the valve will automatically go to the fail position (counterclockwise or clockwise) by means of the springs in the actuator. |
|

-
Springs equal to 100 PSI torque output
-
Limit switch to shut down pump when valve reaches open/closed position
-
Two additional switches for open/close indication
-
Painted carbon steel mounting brackets unless specified otherwise
-
4-20MA positioners in either weather or explosion proof verisions

- M-1 handwheel manual overrides
- Explosion-proof motors, switches and solenoid valves
- Wash down motors
- Heater and thermostats
- Single phase - 120 VAC, 220 VAC, 3-phase voltages
- 4-20MA DC 0 -10 VDC, or 1-5 VDC for modulation
- 4-20MA DC feedback
- Other voltages available on request
NOTE: We prefer to quote actuator to valve mounting hardware in all cases since the power unit reservoir and actuator are provided as a package.

Pump: Gear-Type pump, capacity 3.70 gallons/minute M404 Model. Opening and closing stroke times at +70°F ambient temperature.
| RCI 230SRH-100/M404 ............................3-5 seconds |
| RCI 240SRH-100/M404 ............................5-10 seconds |
| RCI 250SRH-100/M404 ...........................10-15 seconds |
| RCI 260SRH-100/M404 ...........................15-20 seconds |
| RCI 265RH100/M404...............................25-30 seconds |
| RCI 270SRH-100/M404 ...........................35-50 seconds |
| RCI 280SRH-100/M404 ...........................75-100 seconds |
| RCI 88SRH-100/M404 ........................... 250-300 seconds |
| RCI 90SRH-100/M404 ............................ 150-200 seconds |
| RCI 100SRH-100/M404 ............................250-300 seconds |
NOTE: Failure and power stroke times can be altered through variations of the standard package.
| Pump Pressure - Factory set between 100 and 140 PSI |
|
| Motor - 1/2 HP, 3450 RPM, 115/230/60, single phase |
|
| Operating Temperature Range - -5°F to 130°F |
|
| Oil Type - Mobil DTE 24 or equivalent
|
| TECHNICAL DATA
|
|